Research on the Environmental Adaptability of the Secondary Equipment Compartment of Yongji Substation in Jilin Province
The secondary equipment compartment of a substation is a key component of the power system, responsible for installing and managing various control, protection, monitoring, and communication equipment. This means that the secondary equipment compartment needs to have strong adaptability to meet local environmental requirements. Due to the impact of the typhoon, there are waterproofing issues in the secondary equipment compartment of Jilin Yongji Substation. Therefore, it has been improved. On the basis of the original structure, polyurethane insulation boards are added to the inner and outer layers to improve the water absorption of the prefabricated cabin. And environmental adaptability research was conducted on the improved secondary equipment cabin. The analysis mainly focuses on the working conditions of the secondary equipment compartment under extreme temperature, making it practical.
Substation Prefabricated Cabin
电力对社会发展意义重大,在每年增加的电网投资中,变电站的建设投资占据了50%以上比例
预制舱是国家电网基于“标准配送式”这一核心理念的基础上推出的户外模块化智能变电站的重要一环。预制舱是智能变电站应用的新技术、新材料、新设备的一个重要体现,它是由预制舱体、二次设备屏柜或机架、舱体辅助设施等组成,在工厂内完成制作、组装、配线、调试等工作,并作为一个整体运输至工程现场
在变电站设备功能整合研究方面,我国的新一代智能变电站内预制舱对舱内智能照明、暖通设施控制系统的信息传输方式和规约标准进行了研究
总的来说,预制舱变电站是目前电力行业中的一种重要技术创新和发展趋势。本文首先根据传统设计方法对原有二次设备预制舱进行优化;然后用有限元分析法对预制舱整体结构进行风载荷分析、雪压载荷分析、抗震分析;再提出针对永吉地区预制舱保温的创新方法进而进行预制舱结构的优化设计,得到改进后的预制舱三维模型,对预制舱的传统设计和改进后的三维模型结构进行对比分析,得到分析结果,确定最终结构;最终对寒冷地区预制舱进行温控设计,并对预制舱整体进行热环境仿真。本论文对提高寒冷地区预制舱保温隔热效果、设计制造水平、自主开发能力具有积极作用。
变电站二次设备舱是电力系统中的关键组成部分,负责安装和管理各类控制、保护、监测及通信设备。这需要舱体设计坚固,具备防火、防尘和散热功能,内部安装的设备包括保护装置、控制系统、监测仪器和通信设备,用于实时监控和优化电力系统的运行
结构部件 |
材料选型 |
底座骨架 |
底座:250 × 250 × 14 H形钢 屏柜支撑:30a#槽钢 舱底封板:3.0-Q345冷板(双层) 舱底内部材料:岩棉 |
墙体骨架 |
立柱:100 × 150 × 6扁通,100 × 100 × 5方通,100 × 60 × 4扁通 横檀条:60 × 60 × 3方通 角筋:40 × 5等边角铁 |
屋顶骨架 |
横梁:60 × 60 × 3方通 角筋:40 × 5等边角铁 加强拉杆:φ16圆钢 |
顶棚 |
横梁:40 × 40 × 1.5方通 角筋:50 × 30 × 3不等边角铁 顶板:1.5-Q345冷板 |
内墙板 |
采用岩棉聚氨酯复合板(内外都为0.5 mm彩钢板,芯材采用防火性能高于二级的岩棉聚氨酯复合板)。 |
外墙板 |
采用复合板材料,从外到内,采用金邦板、防水透气膜、岩棉板、欧松板,聚氨酯保温板。 |
预制舱体骨架选用型钢。内墙板选用优质热镀锌板,材料机械性能完全能满足轻钢结构强度要求。考虑吉林220 kV永吉变电站所在地区为严寒地区,钢材选用Q345,为低合金钢,塑性和焊接性能良好,低温性能好,可用于−40℃以下环境,相比Q235材质,Q345综合力学性能更好(强度较高、加工和焊接工艺较好),并具有较好的耐磨、耐蚀、耐低温性能。
据吉林市人民政府通告,在2024年7月,永吉县受到了两次重要的降水事件的影响。这反映了该地区在面对自然灾害时的应对挑战,需要采取相应的预防和应对措施来减少可能的灾害影响。降水量的增多也意味着原始预制舱内墙板未考虑降水的问题,易导致预制舱漏水破坏二次舱设备的性能。这需要在顶棚与内外墙板中添加材料使其具备防水性能的同时保留原有的保温效果。经研究,文本将聚氨酯加入到顶棚与内外墙板中。
聚氨酯保温板是一种高效的绝热材料,广泛用于建筑和工业领域。它的核心性能体现在多个方面
本章主要针对预制舱进行在风载荷分析、雪压载荷分析、抗震分析四个方面的有限元仿真分析。分析背景如下:
(1) 模拟预制舱在最大风压0.85 KN/m2的载荷正面吹的情况下,整个模型所受的最大应力位置以及数值,根据材料的屈服强度估算出模型所能承受的最大风压。
(2) 模拟预制舱在最大雪压0.85 KN/m2的载荷作用在屋顶时候,整个模型所受的最大应力位置以及数值,根据材料的屈服强度估算出模型所能承受的最大雪压载荷。
(3) 模拟预制舱在地震烈度等于8 (水平加速度为0.4 g)的情况下,模型各部件最大应力是否超过屈服强度。
材料名称 |
密度(kg/m3) |
弹性模量(MPa) |
泊松比 |
屈服强度(MPa) |
欧松板 |
700 |
6000 |
0.3 |
1 |
金邦板 |
1500 |
3900 |
0.32 |
14 |
Q235钢 |
7900 |
206,000 |
0.29 |
235 |
Q345钢 |
7850 |
206,000 |
0.28 |
345 |
岩棉 |
180 |
6.2 |
0.3 |
0.7 |
聚氨酯保温板 |
40 |
1.5 |
0.3 |
0.4 |
吉林永吉工程项目所在位置为郊区,地面粗糙度按B类地区取值,风速按低于12级风(风速约为36.9 m/s)计算,风载荷计算方法参照GB 50009-2012。垂直于建筑物表面的风载荷标准值按公式(1)计算:
(1)
式中, 为风载荷标准值, 为高度z处的风振系数,按GB 50009-2012规定,预制舱结构可不考虑风压脉动对结构产生风振的影响,遂取值1.0; 为风载荷体型系数,按GB 50009-2012第8.3.1条,当屋面坡度角≤15˚时,取值0.6,本文设计的预制舱顶大于15˚,因此其值大于0.6,考虑原始预制舱,风载荷体型系数取1; 风压高度变化系数,按GB 50009-2012规定,取值1.0; 为基本风压,kN/m2。基本风压按重现期为50a取值,即w0 = 0.85 kN/m2。
表面风压为0.85 kN/m (0.00085MPa),吹风面积为整个竖直墙正面和屋顶正面。舱体受力面积及风向示意图如
预制舱舱体框架模型及风载应力结果仿真示意图如
从0.85 kN/m2风载工况可以看出:模型最大应力出现在屋顶顶棚的方形垫脚上,最大值为211 MPa,小于Q345的屈服强度345 MPa。其余材料部件上的应力远小于相关材料的屈服强度,安全。根据材料在屈服前的线性关系,最大应力达到材料的345 MPa屈服强度的时候最大风压为345 × 0.85/211 = 1.38 (kN/m2)。
积雪以静载的形式对预制舱顶部施加压力,使舱顶构件产生形变,积雪冰冻后温度变化也会改变钢型材结构的刚度特性
(1)
式中, 雪载荷标准值,kN/m2; 屋面积雪分布系数; 基本雪压,kN/m2。
永吉地区基本雪压按50 a重现期的雪压0.85 kN/m2计算;规范规定,当屋面坡度角≤25˚时,雪载应按均匀分布考虑,故
为1.0;雪压载荷为0.85 kN/m2 (0.00085 MPa),雪压面积是整个屋顶斜面。舱体雪压载荷工况示意图如
雪压载荷应力示意图如
预制舱结构固有频率按模态分解法计算,建模时,舱内电力二次设备和围护墙体质量等效施加在承载结构上,从横向和纵向两个方向对结构进行抗震分析。分析条件为:重力加速度为9.8 m/s,由于地震模拟耗时较长,板状部件受地震影响较小,故模拟中省略;模拟为烈度为8的地震,水平加速度最大为0.4 g = 3.95 m/s。本例中X方向作为水平加速度模型受破坏最大,所以选取X方向作为水平加速度施加方向。Z方向固定。水平和竖直加速度幅值曲线选取Abaqus官方实例当中所用的koyna幅值曲线。舱体工况分析示意图如
预制舱舱体抗震应力示意图如
基于热力学仿真软件Flotherm,按照实体模型分别建立复合墙体、顶部保温层、底部保温层以及防静电地板的等效传热模型
为了保证舱内设备正常运行的环境条件,预制舱舱体采用双层保温结构,保温层厚度≥50 mm。隔热保温板采用双层优质钢板(内部填充物采用建设部许可聚氨酯防火保温材料,确保整个预制舱的保温和防火性能) + 环保金属装修层,保证达到“24墙”的保温功效。
本次舱体保温隔热研究采用k-ε双方程湍流模型进行模拟,数值模拟采用由连续性方程、动量守恒方程以及湍流脉动动能方程(k方程)等数学表达式。同时做以下假定:
(1) 预制舱内部空气低速流动且不可压缩,并符合Boussinesq方程假设;
(2) 空气流动为稳态紊流;
(3) 不考虑重力的影响;
(4) 忽略由流体黏性力做功引起的耗散热。
相应环境条件如下:
(1) 环境温度−45℃~+45℃,正常工作状态下舱内温度宜控制在18℃~25℃范围内。在任意一台空调故障时舱内温度可为5℃~30℃范围内。
(2) 屏柜总功率为4080 W。
(3) 空调。两台直流变频风管机,最大制热功率5800 W,最大制冷功率5000 W。
(4) 预制舱采用1个电暖气采暖,壁挂式安装,布置在舱体内长度方向的右侧底部。
(5) 新风系统采用1个抽风风扇及1个吹风风扇设计,目的是提供足够的风压和风量,风扇的风量根据推荐值采用1000 m3/h。预制舱温控系统基本模型如
针对温控系统空调制冷、新风系统制冷、空调加电暖气共同取暖三种情景进行仿真,对总体的温控系统环境温度工作状态区间进行确认和验证。
实验一:温控系统空调制冷仿真。仿真模拟环境温度45℃时,预制舱内温度环境情况,温控系统中设备工作状态为空调开启、电暖气关闭、所有风扇关闭。分别仿真两台空调同时工作和一台空调故障时另一台空调单独工作的情况。
(1) 两个空调同时开启。设定空调出口温度13℃,由于热空气向上流动,高温情况下应重点关注预制舱上部温度情况,因此取距底部2 m高截面进行验证。仿真结果如
图9. 距舱底2 m高度温度截面图
由仿真结果可以看出,当环境温度为45℃且两台空调同时开启时,舱内部空气温度在19℃~24℃之间,满足设计要求。
(2) 单侧空调开启。一台空调故障时另一台空调单独工作,设定空调出口温度10℃。仿真结果如
图10. 距舱底2 m高度温度截面图
由仿真结果可以看出,当环境温度为45℃且单侧空调开启时,舱内部空气温度在21℃~28℃之间,满足单台空调故障时的设计要求。
图11. 距舱底2 m高度温度截面图
实验二:温控系统新风系统制冷仿真。仿真模拟环境温度15℃时,预制舱内温度环境情况,温控系统中设备工作状态为空调关闭、电暖气关闭、所有风扇开启。仿真结果如
由仿真结果可以看出,当环境温度为15℃新风系统开启时,舱内部空气温度在21℃~25℃之间,满足设计要求。
实验三:温控系统空调加电暖气取暖仿真。仿真模拟环境温度−45℃时,预制舱内温度环境情况,温控系统中设备工作状态为空调开启、电暖气开启、所有风扇关闭。分别仿真两台空调同时工作和一台空调故障时另一台空调单独工作的情况。
(1) 两个空调同时开启。设定空调出口温度22℃,由于冷空气向下流动,低温情况下应重点关注预制舱底部温度情况,因此取距底部0.5 m高截面进行验证。仿真结果如
图12. 距舱底0.5 m高度温度截面图
由仿真结果可以看出,当环境温度为−45℃且两台空调,右侧电暖气同时开启时,舱内部空气温度在20℃~23℃之间,满足设计要求。
(2) 单侧空调开启。一台空调故障时另一台空调单独工作,设定空调出口温度22℃。仿真结果如
图13. 距舱底0.5 m高度温度截面图
由仿真结果可以看出,当环境温度为−45℃且单侧空调,右侧电暖气同时开启舱内部空气温度在12℃~22℃,满足单台空调故障时的设计要求。
根据综合仿真结果,以下为总体的温控系统环境温度工作状态区间:
1) −45℃~−5℃为空调加取暖器制热区间。
2) −5℃~0℃为温控系统不工作区间。
3) 0℃~15℃为新风系统工作区间。
4) 15℃~45℃为空调制冷区间。
对变电站二次设备舱结构抗震、抗风、抗积雪荷载及保温性能等方面的分析结果表明,改进的二次设备舱结构具有较强的环境适应性,能够适应永吉地区强风及高寒特点。在材料方面,通过对几种载荷的分析,Q235钢可以很好的使用在预制舱的建设上,仅对于强度要求较高的受力处需要Q345钢,这样大大减少了成本。在保温性研究方面主要对空调和风扇的应用进行了区间划分,节约了能源。且对比原有二次设备舱,通过添加聚氨酯材料解决了永吉变电站预制舱的防水问题。本研究为预制舱结构的设计优化提供了分析方法,为配送式智能化变电站在高寒的推广应用提供了参考依据。
*通讯作者。